IR Value Chart | IR Value Table | IR Value of Motor | IR Value Full Form | IR Value of Transformer
IR stands for Insulation Resistance. It measures the resistance offered by insulating materials to prevent current leakage. Measured in Megaohms (MΩ), IR is a key indicator of the health and safety of electrical equipment like motors, transformers, and cables.
Why is IR Testing Important?
Insulation resistance testing helps detect moisture ingress,
insulation aging, or damage. It ensures safe operation, prevents electrical
hazards, and complies with international testing standards.
What is IR Value?
IR Full Form: Insulation Resistance
IR Value is the measure of resistance offered by insulating materials to current leakage. It is expressed in Megohms (MΩ) and measured using an Insulation Resistance Tester (commonly called a Megger).
Why is Insulation Resistance (IR) Important?
Insulation materials in motors, transformers, and cables can degrade over time due to:
-
Moisture ingress
-
Heat
-
Mechanical damage
-
Contamination
-
Aging
Low IR values can lead to current leakage, short circuits, fire hazards, or equipment failure.
IR testing ensures:
-
Safe operation
-
Preventive maintenance
-
Early fault detection
IR Value Chart | IR Value Table
Rated
Equipment Voltage |
Recommended
Test Voltage (DC) |
Minimum
Acceptable IR Value |
Remarks |
Up to 250 V |
500 V |
≥ 1 MΩ |
Control
cables, small equipment |
251 V – 500 V |
500 V |
≥ 1 MΩ |
LV power
circuits |
501 V – 1000
V |
1000 V |
≥ 1 MΩ |
LV panels,
feeders |
1.1 kV – 11
kV |
2500 V |
≥ 5 MΩ |
MV motors,
transformers |
11 kV – 33 kV |
5000 V |
≥ 10 MΩ |
HV
switchgear, XLPE cables |
Above 33 kV |
5000 V or
higher |
OEM Standard |
PI/DAR ratio
may be used |
IR Value of Motors (New and Used)
New motors should have IR ≥ 100 MΩ. For used motors, the IR
should follow IEEE 43 standard:
IR Value of Transformers and Cables
Equipment
Type |
Test Voltage |
Test Between |
Purpose |
Power Cables |
500V–5kV |
Conductor to
Earth, Phase to Phase |
Detect
insulation failure |
Motors/Generators |
1000V–5000V |
Winding to
Earth, Phase to Phase |
Check winding
insulation |
Transformers |
1000V–5kV |
HV to Earth,
LV to Earth |
Verify
dielectric strength |
Lighting
Circuits |
500V |
Line to
Neutral, Line to Earth |
Avoid short
circuits |
Instruments Used for IR Value Measurement
Accurate IR testing depends on the use of reliable
instruments. These include:
IR Testing Procedure (Summary)
Frequently Asked Questions (FAQ)
What is the full form of IR?
IR stands for Insulation Resistance.
What is a good IR value?
High and stable IR values—usually above 1 MΩ—indicate good
insulation.
How often should IR tests be performed?
During commissioning, regular maintenance, and after
repairs.
What does a low IR value indicate?
Moisture ingress, insulation aging, or internal faults.
What instruments are used for IR testing?
Megger, Digital IR Tester, PI/DAR Tester, Multifunction
Tester.
What is PI (Polarization Index)?
PI = IR@10min ÷ IR@1min. PI ≥ 2 indicates good insulation.
How do I test IR safely?
De-energize, discharge, use PPE, and follow proper
connection and test procedures.