IR stands for Insulation Resistance. It measures the resistance offered by insulating materials to prevent current leakage. Measured in Megaohms (MΩ), IR is a key indicator of the health and safety of electrical equipment like motors, transformers, and cables.

    Why is IR Testing Important?

    Insulation resistance testing helps detect moisture ingress, insulation aging, or damage. It ensures safe operation, prevents electrical hazards, and complies with international testing standards.

    What is IR Value?

    IR Full Form: Insulation Resistance

    IR Value is the measure of resistance offered by insulating materials to current leakage. It is expressed in Megohms (MΩ) and measured using an Insulation Resistance Tester (commonly called a Megger).


    Why is Insulation Resistance (IR) Important?

    Insulation materials in motors, transformers, and cables can degrade over time due to:

    • Moisture ingress

    • Heat

    • Mechanical damage

    • Contamination

    • Aging

    Low IR values can lead to current leakage, short circuits, fire hazards, or equipment failure.

    IR testing ensures:

    • Safe operation

    • Preventive maintenance

    • Early fault detection


    IR Value Chart | IR Value Table

    Rated Equipment Voltage

    Recommended Test Voltage (DC)

    Minimum Acceptable IR Value

    Remarks

    Up to 250 V

    500 V

    ≥ 1 MΩ

    Control cables, small equipment

    251 V – 500 V

    500 V

    ≥ 1 MΩ

    LV power circuits

    501 V – 1000 V

    1000 V

    ≥ 1 MΩ

    LV panels, feeders

    1.1 kV – 11 kV

    2500 V

    ≥ 5 MΩ

    MV motors, transformers

    11 kV – 33 kV

    5000 V

    ≥ 10 MΩ

    HV switchgear, XLPE cables

    Above 33 kV

    5000 V or higher

    OEM Standard

    PI/DAR ratio may be used

    IR Value of Motors (New and Used)

    New motors should have IR ≥ 100 MΩ. For used motors, the IR should follow IEEE 43 standard:

    IR (MΩ) = (Rated kV + 1) × 1 MΩ
    Example: For 6.6 kV motor, IR ≥ 7.6 MΩ

    IR Value of Transformers and Cables

    Equipment Type

    Test Voltage

    Test Between

    Purpose

    Power Cables

    500V–5kV

    Conductor to Earth, Phase to Phase

    Detect insulation failure

    Motors/Generators

    1000V–5000V

    Winding to Earth, Phase to Phase

    Check winding insulation

    Transformers

    1000V–5kV

    HV to Earth, LV to Earth

    Verify dielectric strength

    Lighting Circuits

    500V

    Line to Neutral, Line to Earth

    Avoid short circuits

    Instruments Used for IR Value Measurement

    Accurate IR testing depends on the use of reliable instruments. These include:

    1. Megger: The traditional insulation resistance tester, either analog or digital.
    2. Digital Insulation Resistance Testers: Offer auto-ranging, memory, and Bluetooth features.
    3. Analog Insulation Testers: Simple and durable; preferred in field conditions.
    4. Multifunction Testers: Include IR testing plus RCD, loop, and voltage testing.
    5. PI & DAR Testers: For polarization index and dielectric absorption ratio tests.
    6. Online IR Monitoring Systems: Provide real-time monitoring without needing shutdown.
    IR Value Chart | IR Value Table

    IR Testing Procedure (Summary)

    1. De-energize and isolate the system.
    2. Discharge any stored energy.
    3. Connect the megger properly.
    4. Select appropriate test voltage.
    5. Apply voltage for at least 60 seconds.
    6. Record readings in MΩ.

    Frequently Asked Questions (FAQ)

    What is the full form of IR?

    IR stands for Insulation Resistance.

    What is a good IR value?

    High and stable IR values—usually above 1 MΩ—indicate good insulation.

    How often should IR tests be performed?

    During commissioning, regular maintenance, and after repairs.

    What does a low IR value indicate?

    Moisture ingress, insulation aging, or internal faults.

    What instruments are used for IR testing?

    Megger, Digital IR Tester, PI/DAR Tester, Multifunction Tester.

    What is PI (Polarization Index)?

    PI = IR@10min ÷ IR@1min. PI ≥ 2 indicates good insulation.

    How do I test IR safely?

    De-energize, discharge, use PPE, and follow proper connection and test procedures.